1/31/23 Huestis Hall Suite 34 Exhaust and HVAC Air Supply Shutdown

Begin:  Tuesday, January 31, 2023, at 9:00 am

End:      Tuesday, January 31, 2023, at 12:00 noon

Building(s) or Area(s) Affected:  Huestis Hall Basement Suite 34

Scope:  As part of the Huestis Renovation project, Siemens will temporarily shut down network connectivity to BAS devices in the Zebrafish Quarantine facility via PXCM71 and associated DXRs.

Services Impacted:  This will affect supply and exhaust air to Suite 34.

Work Performed By:  Siemens

ContactMartina Oxoby, CPFM Owner’s Representative, 541-346-5880

Current construction and impacts information can be found on the UO Maps site.

1/31/23 Huestis Hall Suite 34 Exhaust and HVAC Air Supply Shutdown

Begin:  Tuesday, January 31, 2023, at 9:00 am

End:      Tuesday, January 31, 2023, at 12:00 noon

Building(s) or Area(s) Affected:  Huestis Hall Basement Suite 34

Scope:  As part of the Huestis Renovation project, Siemens will temporarily shut down network connectivity to BAS devices in the Zebrafish Quarantine facility via PXCM71 and associated DXRs.

Services Impacted:  This will affect supply and exhaust air to Suite 34.

Work Performed By:  Siemens

ContactMartina Oxoby, CPFM Owner’s Representative, 541-346-5880

Current construction and impacts information can be found on the UO Maps site.

1/30/23 – Unknown – Tykeson Hall Elevator Intermittent Shutdown Advisory

UPDATE 2/1/23:
The elevator is now operational, but as mentioned, it will be working intermittently until the part arrives.  Please let us know if you find it offline and we will dispatch Otis to restore it.

If you have concerns about accessing your workplace when elevator services are impacted, please contact your supervisor to find an appropriate accommodation.

 

Begin:  Monday, January 30, 2023 – effective immediately

End:      Unknown

Building(s) or Area(s) Affected:  Tykeson Hall Elevator

Scope:  The elevator is currently offline and is being worked on by Otis.  Until the needed part arrives, the elevator will work intermittently.   Please alert Work Control Center when the elevator is down, and we will dispatch Otis to restore it to service.  Updates will be sent when we have more information.

Services Impacted:  The elevator is not operational.  Please use the stairs.

Special Instructions:  If you have concerns about accessing your workplace when elevator services are impacted, please contact your supervisor to find an appropriate accommodation.

Work Performed By:  Otis Elevator

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/26/23 Klamath Hall RO Water Shutdown

Begin:  Thursday, January 26, 2023, at 7:00 am

End:      Thursday, January 26, 2023, at 3:00 pm

Building(s) or Area(s) Affected:  Klamath Hall

Scope:  Due to leak in room #132 Klamath, RO water system for entire building needs to be turned off and drained.

Services Impacted:  RO/DI water will be offline during this time.

Work Performed By:  CPFM FS Crew

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/25/23 – 1/27/23 Fine Arts Metalsmithing, Jewelry, and Woodshop Service Alley Closure

Begin:  Wednesday, January 25, 2023

End:      Friday, January 27, 2023

Building(s) or Area(s) Affected:  Woodshop and Fine Arts Metalsmithing & Jewelry buildings

Scope:  Due to tree relocation work, the service alley between the Woodshop and Fine Arts Metalsmithing & Jewelry buildings will be closed. Trees will be relocated to and planted at the Urban Farm Riverside site.

Services Impacted:  This will affect access to the service alley between Woodshop and Fine Arts Metalsmithing & Jewelry buildings – see attached logistics plan

Work Performed By:  Hoffman Construction

ContactDenise Stewart, CPFM Owner’s Representative, 541-346-2280 or 541-335-1258

Current construction and impacts information can be found on the UO Maps site.

Tree Relocation Closure

1/25/23 CPFM Admin Quonset #136 and Surrounding Buildings Steam Heat Shutdown

UPDATE:
The steam valve repair was completed ahead of schedule. The steam is now back on (11:45 am) to CPFM ADMIN and related Quonsets.

 

Begin:  Wednesday, January 25, 2023 at 11:00 am

End:      Wednesday, January 25, 2023 at 3:00 pm

Buildings Affected:  CPFM Admin Quonset, FS Exterior Storage 2, Lock and Door Shop, MNCH Archaeological Research Lab, Paleoecology Research,  Archaeology Research, MNCH Prep Lab, FS Storage

Scope:  Due to a leaking main steam valve, building steam heat will be shut down briefly to replace the main exterior valve gaskets and seals.

Services Impacted:  Building heat will be off to the buildings listed above – see map below.

Work Performed By:  CPFM Utilities & Energy

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/24/23 Fine Arts Studios and Millrace Studios Emergency Domestic Water Shutdown

UPDATE:
The water has been restored.

 

Begin:  Tuesday, January 24, 2023 – effective immediately

End:      Unknown

Building(s) or Area(s) Affected:  Millrace 1, 2, and 3, and all Fine Arts Studios

Scope:  Emergency shutdown of domestic water due to contractor hitting the water line at the north end of the parking lot, behind Knight Campus.  Domestic water will be offline until repairs can be made.  An update will be sent when water has been restored.

Services Impacted:  Domestic water not available.

Work Performed By:  CPFM Facilities Crews

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/24/23 Oregon Hall Steam Heat and Hot Water Shutdown

UPDATE:
The steam was restored today at 1:45 pm.

 

Begin:  Tuesday, January 24, 2023 at 11:00 am

End:      Tuesday, January 24, 2023 at 3:00 pm

Building(s) or Area(s) Affected:  Oregon Hall

Scope:  Due to a failed steam pressure relief valve, building steam heat and hot water will be briefly shutdown to replace the valve.

Services Impacted:

  • Domestic hot water and building steam heat will be offline during this time.
  • Work will take place in the utility tunnel and mechanical room 001.

Work Performed By:  CPFM Utilities & Energy

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/24/23 Huestis Basement Fire Alarm System Shutdown Advisory

Begin:  Tuesday, January 24, 2023, at 6:00 am

End:      Tuesday, January 24, 2023, at 2:00 pm

Building(s) or Area(s) Affected:  Huestis Hall Basement

Scope:  As part of the Huestis Renovation project, the fire suppression system serving the basement will be shut down to temporarily move pipes to accommodate concrete work.

Details:  Horns, Strobes, and Speakers on the fire alarm system will not sound after the scheduled time. Provisions have been taken to monitor the building fire systems during this time and alarms that occur after the scheduled time should be considered real events and occupants should evacuate as usual per the U of O Emergency Procedures.

Special Instructions:  If there are questions regarding emergency evacuation, please visit Emergency Management & Continuity, https://safety.uoregon.edu/evacuations

Work Performed By:  Harvey & Price

ContactMartina Oxoby, CPFM Owner’s Representative, 541-346-5880

Current construction and impacts information can be found on the UO Maps site.

1/23/23 – 1/25/23 Tykeson Hall Elevator Emergency Shutdown

UPDATE:
The elevator has been restored to service.

 

Begin:  Monday, January 23, 2023 – effective immediately

End:      Unknown

Building(s) or Area(s) Affected:  Tykeson Hall Elevator

Scope:  The elevator is offline and is awaiting a part.  It is unknown, at this time, when the part will arrive.  An update will be sent out when we have more information.

Services Impacted:  The elevator is not operational.  Please use the stairs.

Work Performed By:  Otis Elevator

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

To view current construction and impacts, visit UO Map.

1/23/23 – 1/25/23 Huestis, Klamath, LISB, Streisinger, Willamette, and ZIRC Autoclave Steam Shutdown

Begin:  Monday, January 23, 2023, at 5:00 am

End:      Wednesday, January 25, 2023, at 4:00 pm

Building(s) or Area(s) Affected:  Huestis Hall, Klamath Hall, Lewis Integrative Science Building (LISB), Streisinger Hall, Willamette Hall, Zebrafish International Resource Center (ZIRC)

Scope:  Due to the failure of a steam expansion joint on the clean steam line to campus, all clean steam fed from CPS will be shut down to make repairs. The pipeline alignment, pipe supports, and damaged insulation will be replaced as part of the project.

Services Impacted:

  • This will affect clean steam in the buildings listed above.
  • Work will take place in the tunnel near Knight Campus.

Work Performed By:  S2 Industrial

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Current construction and impacts information can be found on the UO Maps site.

1/20/23 Lewis Integrative Science Building Leak – User Update

In the early hours of January 19, 2023, a water leak occurred within the water softener system in LISB room 307B. The leak impacted several spaces on the 2nd and 3rd floors of the building. Thanks to the quick work of CPFM staff, the impacts were contained and limited to some cabinetry, carpet, ceiling tiles, and/or gypsum board wall finishes in the rooms listed below.

201, 204, 206, 206A, 206B, 207, 207D, 303C, 304, 307, 307A, and 307B.

The University has retained a mitigation contractor, Belfor, to provide mitigation services for all of the affected spaces. Our current mitigation strategy will be to dry out finishes in place, with minimal demolition. This will include the use of dehumidification equipment and large fans strategically placed throughout affected areas. The equipment will generate heat and a significant amount of noise. EHS will oversee the dry out phase of the mitigation. Once mitigation has been completed, the space will be reassembled by CPFM staff. Belfor will be setting up mitigation equipment in the affected spaces this afternoon (January 20, 2023) to run over the weekend. Dry out status will be re-evaluated on Monday (January 23, 2023).

Please feel free to contact me if you have any questions or concerns about the mitigation phase of this incident. If any non-building related items were damaged as a result of this incident, contact Risk Management at 541-346-8316.

__________________________________

Nate Ferguson

Building Environmental Sciences Coordinator

http://safety.uoregon.edu/

 

Safety & Risk Services | University of Oregon
1260 University of Oregon | Eugene, OR 97403-1260

Office: 541.346.2901 | Mobile: 530.902.0109

1/19/23 East 13th Developments and Safety Plan

A traffic control plan has been approved and will be implemented in phases. The fence line has already been moved back to the north curb, allowing west bound bicycle traffic.

 

By the end of this week (1/20/23), the city plans to install water filled barriers on the portion of the street that currently has the dashed bike lane lines. This will create a protected bike/ped area on the north side of the street. This is intended to function as shared use path with both bikes and peds traveling both directions

 

On the south side of the street, the existing back-in parking will be removed to create an eastbound vehicle lane allowing LTD buses and other vehicles through. There will initially be a parallel parking area on the far south side of the street. This will convert to a pedestrian path when the Taylor’s redevelopment takes over the sidewalk on the south side.

1/17/23 Prince Lucien Campbell 3rd Floor Fire Alarm System Work and Testing Advisory

REVISED DATE:
The date has been changed to the following day, Tuesday, January 17.

 

BeginMonday, January 16, 2023, at 7:00 am  Tuesday, January 17, 2023, at 7:00 am

End:      Monday, January 16, 2023, at 3:00 pm  Tuesday, January 17, 2023, at 3:00 pm

Building(s) or Area(s) Affected:  Prince Lucien Campbell 3rd floor

Scope:

  • In association with the remodeling work taking place in rooms 348 and 353, IES will put the fire panel in test mode for the third floor.
  • Harvey & Price will then install fire sprinkler piping in the ceiling space of room 348.
  • Once piping is installed and tested, IES will put the fire panel back on line.
  • GBC Construction will provide fire watch personnel for the third floor during this time.

Details: Horns, Strobes, and Speakers on the fire alarm system will not sound after the scheduled time. Provisions have been taken to monitor the building fire systems during this time and alarms that occur after the scheduled time should be considered real events and occupants should evacuate as usual per the U of O Emergency Procedures.

Special Instructions: If there are questions regarding emergency evacuation, please visit Emergency Management & Continuity, https://safety.uoregon.edu/evacuations

Work Performed By:  EIS, Harvey & Price, GBC Construction

ContactGene Mowery, CPFM Owner’s Representative, 541-346-5593 or 541-799-4016

Current construction and impacts information can be found on the UO Maps site.

1/17/23 – 1/19/23 JSMA Large Sculpture Installation Advisory

Begin:  Tuesday, January 17th, 2023, at 7:00 am

End:      Thursday, January 19th, 2023, at 5:00 pm

Building(s) or Area(s) Impacted:  Jordan Schnitzer Museum of Art

Scope:  A large-scale sculpture will be installed in the JSMA’s North Courtyard during the third week of January.

Services Impacted:

  • This will impact the JSMA’s parking lot (including one ADA parking spot), loading dock, security entrance, bike cage, trash collection, north courtyard, north sidewalk.
  • Crane staging and art uncrating will be located in the JSMA’s parking lot.
  • There will be limited access to the west end of Johnson Lane.

Work Performed By:  Artech, Ness Campbell, JSMA staff

ContactMiranda Callander, Jordan Schnitzer Museum of Art, 541-346-0970

To view current construction and impacts, visit UO Map.

1/11/23 – 1/12/23 Gerlinger Hall and Gerlinger Annex Noise Advisory

Begin:  Wednesday, January 11th, 2023 at 8:00 am

End:      Thursday, January 12th, 2023 at 3:30 pm

Building(s) or Area(s) Affected:  Gerlinger Hall and Gerlinger Annex

Scope:  Pressure washing will be performed to remove moss from the Northwest entryway to Gerlinger Annex

Services Impacted:  Noise from this work may be heard inside Gerlinger Hall and Gerlinger Annex

Work Performed By:  CPFM Facilities Services Maintenance Shop

ContactWork Control Center, Campus Planning and Facilities Management, 541-346-2319

Information on current construction and impacts can be found at UO Maps

1/03/23 Klamath Hall Electrical Panel Shutdown

UPDATE:
Power was restored to Klamath Hall.  All electrical is back in normal status.

 

UPDATE:
The Onyx Bridge east elevator will also be down during this time.

 

Begin:  Tuesday, January 3rd, 2023, at 9:00 am

End:      Tuesday, January 3rd, 2023, at 1:00 pm

Building Affected:  Klamath Hall

Scope:  The main electrical panels will be shut down to evaluate components and test breakers after water intrusion that occurred on 12/10/22.

Services Impacted:  This will affect the electrical power, exhaust, fume hoods, heating, HVAC Air Supply, lab vacuum, and elevator.

Special Instructions:

  • Please shut down and unplug all multi-function copier devices as well as any printers during scheduled power outages. The software on these machines can be negatively affected due to the power surge when the power is turned back on.  A power surge can corrupt the clone files in the machines and change preconfigured settings.
  • Fume hood sashes should be closed and containers within the fume hoods sealed prior to this date.

Work Performed By:  Outside Contractor

ContactWork Control Center, Campus Planning and Facilities Management, 346-2319

To view current construction and impacts. visit UO Map.

1/03/23 – 1/20/23 Knight Library Room 57 Renovation Work and Access Advisory

Begin:  Tuesday, January 3rd, 2023

End:      Friday, January 20th, 2023

Building(s) or Area(s) Affected:  Knight Library Room 57

Scope:  Renovation work is being done in room 57.  A flexible fresh air duct will be run down hall H57 and out the window of room 19 for two days only, January 4th and 5th.  This may cause some ADA access issues. Paint, carpet and other refresh work will follow in room 57

Services Impacted:

  • Access may be affected in Hallway H057 on Wednesday, January 4th, and Thursday, January 5th.
  • Construction noise and odor can be expected in the area.

Work Performed By:  PMG Demolition and CPFM Facilities Services

ContactJanell Cottam, CPFM Owner’s Representative, 541-346-7536

Current construction and impacts information can be found on the UO Maps site.

1/03/22 CANCELLED: Huestis Hall HVAC Exhaust and Air Supply Shutdown

UPDATE 12/29/22:  This shutdown is no longer necessary and has been cancelled.

Begin:  Tuesday, January 3rd, 2023 at 7:00 am

End:      Tuesday, January 3rd, 2023 at 12:00 pm

Building(s) or Area(s) Affected:  Huestis Basement

Scope:  Exhaust Fans 1 & 2 as well as Air Handling Units 1 & 2 will be shutdown to allow for temporary electrical reroutes out of the construction zone as part of the Huestis Hall Renovation project

Services Impacted:  This will affect the air supply and exhaust systems to the zebrafish facility in the basement while the work is being performed

Work Performed By:  Lewis and EC

ContactMartina Oxoby, CPFM Owner’s Representative, 541-346-5880

Current construction and impacts information can be found on the UO Maps site.