[INNOVATION CENTER] Air Supply Shutdown 7/20

Due to preventative maintenance on the building mechanical systems, the air supply to the building will be temporarily shut down July 20, 2018, from 7:30 am – 1:00 pm. This will impact air, heating, cooling and fume hoods in rooms 113N, 113S, 114, 116, and 120.


For questions or concerns please contact CPFM Facilities Services Richard Vaughan at 541-255-5947 or Work Control at 541-346-2319.

[PACIFIC HALL] HVAC SHUTDOWN 8/11

The south wing supply and exhaust HVAC systems need to be turned off  August 11, 2018, from 6:00 am – 8:00 pm to facilitate work on the 3rd floor. Fume hoods will need to be properly secured by Friday afternoon so that EHS can verify the system can be turned off. This will affect all of the new labs in the south wing renovation area.

For questions or concerns please contact CPFM Design and Construction Manager Nick Pritchard at 541-346-9139.

[HUESTIS] Supply Air Shutdown 7/3

As part of the Huestis 2nd floor project, a 24 hr supply air shutdown will be required on July 3, 2018. Supply fan 1A and 3A will be shutdown at approximately 10 am and 1 pm respectively.  The supply air will be restored on the morning of July 5th.

The general exhaust and fume hoods will not be shutdown as part of the shutdown.

Attached is an exhibit that shows the impacted areas. Spaces with an exterior window on the 2nd and 3rd floor will likely observe increased temperatures in the afternoon of t July 3, during the shutdown.


Supply fan 1A: 129, 229, 233 337
Supply fan 3A: 125, 224, 226, 227, 228, 230, 235, 321, 324, 325, 327, 328, 330, 332
Room numbers include the sub-rooms 

For questions or concerns about this project or outage, contact Colin Brennan, CPFM Design and Construction at (541) 346-8242.

 

6/5 – 6/8: [PACIFIC HALL] Air Balancing Contractor Access Advisory

Building Occupants,

 

As part of the ongoing Pacific B-2 Renovation, contractor Air Inc. will be starting to balance the north wing HVAC system. This will be a process over the summer as we finalize spaces and verify space requirements. This work will not disrupt building systems but will require 2-3 people going into each area to verify HVAC grilles and balance those systems. Some ladder work will be necessary.

 

Phase 1 Schedule

Area: Date:
North Wing Basement Tuesday, 6/5
North Wing 1st Floor Wednesday, 6/6
North Wing 2nd Floor Thursday, 6/7
North Wing 3rd Floor Friday, 6/8

For questions or concerns, please contact CPFM Design and Construction Project Manager Nick Pritchard  541-346-9139.

 Future phases will be scheduled in the coming weeks and updates will be provided.

PAC Testing & Balancing (1)-2bc16pd

6/15: [STUDENT REC CENTER] HVAC Air Supply Shutdown Suites 90, 92, 190 & 192

Building Occupants,

Starting June 15, 2018, at 8:00 am the HRV-3 that serves the locker rooms in Suites 90, 92, 190 and 192 will be temporarily shut down while contractors HSW and Alliant seal existing duct work on the system. This will impact HVAC air supply. The Project Manager anticipates that services will be restored approximately 48 hours after the work is completed.

For questions or concerns please contact CPFM Design and Construction Owners Representative Charlene Lindsay at 541-346-5503.

5/24: Huestis Hall HVAC Testing

Campus community,

On Thursday, May 24, Huestis Hall will undergo periodic testing of the building HVAC systems, which handle heating, cooling, and ventilation. This will cause brief interruptions in the climate control and ventilation throughout the building between the hours of 4:00p-5:30p. If you have questions or concerns, please contact Bruce Budzik , Owner’s Representative with Design & Construction at 6-8834.

 

3/28: Intermittent Heating, Cooling and Air supply Disruptions

 Building Occupants,

Due to scheduled preventative maintenance the Zebrafish International Resource Center may experience intermittent heating, cooling and air supply disruptions on March 28, 2018 from 8:00 am – 3:30 pm.

 

For questions or concerns contact CPFM Facilities Services TM2  Mike Allen 541-346-2015 or CPFM Work Control Customer Service Center at 541-346- 2319.

3/14: [MCARTHUR COURT] Preventative Maintenance

This notice has been sent to primary building contacts.

Building Occupants,

Due to scheduled preventative maintenance on McArthur Court building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on March 14, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

3/14: [ESSLINGER] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Esslinger building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on March 14, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

3/7: [KLAMATH] Air Handler Maintenance

This notice has been sent to all building users in Klamath Hall.

 Building Occupants,

Due to scheduled preventative maintenance please keep fume hood sashes down during the below scheduled times in Klamath.

Special Instructions:

The fume hoods cannot be used and all chemical containers should be closed during the indicated time.

 

Date Time Location
3/07/18 8:00 am – 11:00 am North fume hoods affect North end of building basement and 3rd floor.
3/07/18 12:30 pm – 3:00 pm South fume hoods affect South end of building basement and 3rd floor

 

This will impact fume hood exhaust and HVAC Air Supply building wide.  This work is necessary due to filter changes on the air handler units.

For questions or concerns contact CPFM Facilities Services TM2  Mike Allen 541-346-2015 or CPFM Work Control Customer Service Center at 541-346- 2319.

2/21: [WILLAMETTE] Air Handler Maintenance

This notice has been sent to all building users in Willamette.

Building Occupants,

Due to scheduled preventative maintenance please keep fume hood sashes down during the below scheduled times in Willamette.

Date Time Location
2/21/18 8:00 am – 12:00 pm (noon) Eastside Fume Hoods & Westside Supply Air
2/21/18 12:30 pm – 3:00 pm Westside Fume Hoods & Eastside Supply Air

This will impact fume hood exhaust and HVAC Air Supply building wide. This work is necessary due to filter changes on the air handler units.

For questions or concerns contact CPFM Facilities Services TM2 Mike Allen 541-346-2015 or CPFM Work Control Customer Service Center at 541-346- 2319.

[HEDCO] Thermal Comfort Questionnaire & Brief Temperature Fluctuations

This notice has been sent to all building users in HEDCO

Building Occupants,

You are receiving this email because Campus Planning and Facilities Management (CPFM) will soon be performing work on your building’s thermal control systems. The work will identify and correct malfunctioning components and overhaul control routines in an effort to improve thermal comfort in your work space while reducing the building’s energy consumption.

We are surveying building occupants as part of the process to establish a baseline for workplace thermal comfort and to guide these tuning efforts. If you would like to provide feedback, please follow the link to the Thermal Comfort Questionnaire.

Thermal Comfort Questionnaire

Participation should take approximately five minutes and is anonymous and entirely voluntary. Your response will support both this and future building improvement projects on campus and may be used to inform future architectural design research. If you have any questions, please contact Paul Ward at pward@uoregon.edu.

You may experience brief temperature fluctuations during the repair and tuning process over the next four weeks. We are collaborating with CPFM to monitor interior conditions closely and will make every effort maintain temperatures within a comfortable range. If you experience uncomfortable conditions, please contact the CPFM Work Control and Customer Service Center at 541.346.2319.

 

 

 

 

2/20: [HUESTIS] Supply Fan (SF-2) Shutdown

This notice has been sent to all building users.

Building Occupants,

On Tuesday, February 20, 2018, from 9:00 am – 11:00 am supply fan (SF-2) will be temporarily shut down in Huestis.  This may impact rooms with animal research. Fume hoods will operate but may have an INCREASED airflow during the shutdown.  This is necessary due to the replacement of the re-heat temperature sensor inside the air handler.

Impacted Areas:

FIRST FLOOR:
112, 112A, 112B, 112C
120C, 120D, 120E, 120F, 120G
130, 130A, 130B, 130C

SECOND FLOOR:
206, 206A, 206B, 206C
212A
214A
228A
230A
238, 238A, 238B, 238C

THIRD FLOOR:
306, 306A, 306B, 306C
314C
330A
334, 334A, 334B, 334C, 334D

For questions or concerns, please contact CPFM Facilities Service BAS Manager David Ward 541-346-2303.

2/14/18: Huestis Supply Air Shutdown

This notice has been sent to all building users.

 Building Occupants,

 

On Wednesday, February 14, 2018, there will be two intermittent supply air shutdowns at Huestis impacting building exhaust and HVAC Supply air.  This work is necessary due to filters changes on the air handler units.

  • North Side of Building 8:00 am – 10:00 am
  • South Side of Building 1:00 pm – 3:00 pm

For questions or concerns please contact CPFM Facilities Services Zone B Maintenance Manager Bruce Budzik at 541-346-8834.

2/7/18: Chiles Air Handling Unit Shutdown

Building Occupants,

On Wednesday, February 7th, from 8:00 am until 3:30 pm, scheduled preventative maintenance will cause intermittent shutdowns on air handling units and restroom exhaust fans while system filters are changed.

Work will be performed by CPFM crews.

For questions or concerns about how this may impact your area, contact Jim Cody, Campus Planning and Facilities Management (CPFM) Zone A Maintenance Manager at 346-2302.

2/7/18: Peterson Hall Air Handling Unit Shutdown

Building Occupants,

On Wednesday, February 7th, from 8:00 am until 3:30 pm, scheduled preventative maintenance will cause intermittent shutdowns on air handling units and restroom exhaust fans while system filters are changed.

Work will be performed by CPFM crews.

For questions or concerns about how this may impact your area, contact Jim Cody, Campus Planning and Facilities Management (CPFM) Zone A Maintenance Manager at 346-2302.

2/7/18: UO Annex Air Handling Unit Shutdown

Building Occupants,

On Wednesday, February 7th, from 8:00 am until 3:30 pm, scheduled preventative maintenance will cause intermittent shutdowns on air handling units and restroom exhaust fans while system filters are changed.

Work will be performed by CPFM crews.

For questions or concerns about how this may impact your area, contact Jim Cody, Campus Planning and Facilities Management (CPFM) Zone A Maintenance Manager at 346-2302.

2/3 – 2/4: [PACIFIC HALL] Air Supply Fan Shutdown

Update:  Adjusted header dates to match content (originally read as 2/2 – 2/3)

Building Occupants,

February 3-4, 2018 the building air supply fan will need to be shut down due to roofing repairs on the east side of the building, in front of the fresh air intake.  This will impact the HVAC air supply for the entire building.

For questions or concerns, please contact CPFM Design and Construction Project Manager Nick Pritchard  541-346-9139.

Pacific Hall B-2 Outage Timeline 9/9- 12/18

1/31: [CONDON HALL] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Condon Hall building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on January 31, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

1/31: [Prince Lucien Campbell Hall] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Prince Lucien Campbell Hall building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on January 31, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

1/24: [MCKENZIE HALL] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on McKenzie Hall building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on January 24, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

 

1/17: [DEADY HALL] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Deady building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on January 17, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

1/17: [VILLARD HALL, MILLER THEATER COMPLEX] Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Miller Theater Complex building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on January 17, 2018, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.

12/20: Lillis Preventative Maintenance

Building Occupants,

Due to scheduled preventative maintenance on Lillis building equipment, building occupants should expect intermittent shutdowns on air handling units and restroom exhaust fans to allow crews to change system filters. This scheduled work will be taking place on December 20, 2017, from 8:00 am – 3:30 pm.

For questions or concerns please contact CPFM Facilities Services Zone A Maintenance Manager Jim Cody at 541-346-2302.